The dry type cast resin transformer shall be suitable for usage under expected climate conditions. It shall be self-extinguishing and shall not produce toxic gases in the event of fire. This is verified by the Climatic, Environmental and Fire withstand behaviour test as per 60076-11. This paper gives the design features of a 1600 kVA dry type cast resin transformer which was subjected to climatic, environmental and fire behaviour (C2 E2 F1) tests at KEMA testing laboratory, Netherlands. The technical parameters of epoxy resin system, winding configuration, and clamping, etc. necessary to meet the requirements are also discussed.
Published in | American Journal of Electrical Power and Energy Systems (Volume 7, Issue 1) |
DOI | 10.11648/j.epes.20180701.12 |
Page(s) | 11-15 |
Creative Commons |
This is an Open Access article, distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution and reproduction in any medium or format, provided the original work is properly cited. |
Copyright |
Copyright © The Author(s), 2018. Published by Science Publishing Group |
Cast Resin Transformer, C2 E2 F1 Test, Dry Type Transformers, Special Test for Power Transformers
[1] | IEC 60076–11 - (2004) - dry type transformers. |
[2] | IEC 60332–3–10 - Test for vertical flame spread of vertically mounted bunched wires or cables. |
[3] | Hunstman datasheet for Araldite casting system. |
[4] | C57.12.91-2011 - IEEE Standard Test Code for Dry-Type Distribution and Power Transformers. |
[5] | C57.12.01-2015 – IEEE Standard for General Requirements for Dry-Type Distribution and Power Transformers. |
[6] | IEC 60076-1; 2011 Power Transformers part 1 General. |
[7] | IEC 60076-3 – Power Transformers Part 3 Insulation levels, dielectric test and external clearances. |
[8] | Federal Transformers – technical brochure “Cast Resin Transformers” |
[9] | IEC 60085 – Electrical insulation - Thermal evaluation and designation. |
[10] | IEC 60270 – High Temperature techniques – Partial Discharge Measurements. |
APA Style
Remya Krishnan, Muraleedharan Nair. (2018). Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer. American Journal of Electrical Power and Energy Systems, 7(1), 11-15. https://doi.org/10.11648/j.epes.20180701.12
ACS Style
Remya Krishnan; Muraleedharan Nair. Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer. Am. J. Electr. Power Energy Syst. 2018, 7(1), 11-15. doi: 10.11648/j.epes.20180701.12
AMA Style
Remya Krishnan, Muraleedharan Nair. Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer. Am J Electr Power Energy Syst. 2018;7(1):11-15. doi: 10.11648/j.epes.20180701.12
@article{10.11648/j.epes.20180701.12, author = {Remya Krishnan and Muraleedharan Nair}, title = {Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer}, journal = {American Journal of Electrical Power and Energy Systems}, volume = {7}, number = {1}, pages = {11-15}, doi = {10.11648/j.epes.20180701.12}, url = {https://doi.org/10.11648/j.epes.20180701.12}, eprint = {https://article.sciencepublishinggroup.com/pdf/10.11648.j.epes.20180701.12}, abstract = {The dry type cast resin transformer shall be suitable for usage under expected climate conditions. It shall be self-extinguishing and shall not produce toxic gases in the event of fire. This is verified by the Climatic, Environmental and Fire withstand behaviour test as per 60076-11. This paper gives the design features of a 1600 kVA dry type cast resin transformer which was subjected to climatic, environmental and fire behaviour (C2 E2 F1) tests at KEMA testing laboratory, Netherlands. The technical parameters of epoxy resin system, winding configuration, and clamping, etc. necessary to meet the requirements are also discussed.}, year = {2018} }
TY - JOUR T1 - Climatic, Environmental and Fire Behaviour (C2 E2 F1) Test of Cast Resin Transformer AU - Remya Krishnan AU - Muraleedharan Nair Y1 - 2018/04/02 PY - 2018 N1 - https://doi.org/10.11648/j.epes.20180701.12 DO - 10.11648/j.epes.20180701.12 T2 - American Journal of Electrical Power and Energy Systems JF - American Journal of Electrical Power and Energy Systems JO - American Journal of Electrical Power and Energy Systems SP - 11 EP - 15 PB - Science Publishing Group SN - 2326-9200 UR - https://doi.org/10.11648/j.epes.20180701.12 AB - The dry type cast resin transformer shall be suitable for usage under expected climate conditions. It shall be self-extinguishing and shall not produce toxic gases in the event of fire. This is verified by the Climatic, Environmental and Fire withstand behaviour test as per 60076-11. This paper gives the design features of a 1600 kVA dry type cast resin transformer which was subjected to climatic, environmental and fire behaviour (C2 E2 F1) tests at KEMA testing laboratory, Netherlands. The technical parameters of epoxy resin system, winding configuration, and clamping, etc. necessary to meet the requirements are also discussed. VL - 7 IS - 1 ER -